JKW18 Intelligent Reactive Compensation Controller
Technical Data:
Rated Voltage (Un): |
220,230,240 VAC (Phase –Neutral Connection ) |
380,400,415 VAC(Phase-Phase Connection) |
|
Operating Voltage Range: |
(0.9-1.1)x Un |
Rated Current(In): |
…./5A |
Operating Current Range: |
(0.91-1.1) X In |
Rated power: |
Voltage: 3VA-10VA |
Output Contact: |
3A, 750 VA (NO Contact) |
No-Voltage Feature: |
in case of power failure longer than 200 msec. all capacitor steps are disconnected automatically . |
Setting Range: |
C/K:0.02-1.0 Steps: 1-12 COS¢ :0.85(ind.)-1.00 |
CTR:5-6000 Time:2-50 sec, Program:PS1-PS5 |
|
Over Voltage: 220-260V(380V-500V) |
|
Factory Set Value: |
COS¢=1.00(ind.),Step =12 ,Time=7(sec) |
Program=PS1, C/K=0.05, CTR=500 |
|
Over voltage:240v/430v |
|
Ambient Temperature: |
-25degree -55degree. |
Display: |
4 Digit, Red Display. |
Equipment Protection Class: |
Double Insulation- Class II |
Wire Section (For Terminal Block): |
2.5mm2 |
Terminal Block Protection Class: |
IP 00 |
Protection Class: |
IP 20 |
Connections: |
Socket terminal with screw |
Dimension : |
Type PR16 |
Switchboard Cut-out : |
139X139MM |
Weight: |
0.8kg |